EnerTec
Energy Under Control

RGK50

Programmable Controller for Generating Set

BENEFITS

  • Outstanding functions & user-friendliness
  • Complete protection & data display
  • Optional remote communication simplified
  • Ideal for export projects
  • Reliable at extreme temperatures

FEATURES

  • For AC systems from 120 to 600 Vac, 1 & 3 phases, 50 & 60Hz
  • Complete power & instrumentation display
  • Normal & Generator power information display
  • Automatic or manual start possibility
  • Telecommunication interface included (RS-232)
  • Terminal accepts #10 gauge wire
  • Complete documents for the installation & setup
  • CSA Approved (UL & cUL)
  • Temperature and oil pressure sender selected
  • Large LCD graphic display with backlight, functional at -30°C
  • Liquid proof (IP 64) Front panel
  • No PT's are required for nominal voltage system ≤ to 600 Vac
  • Quick-connect terminal block
  • Operating temperature from -30C to 60C
  • 12 programmable digital [contact] inputs
  • 7 internal output relays
  • Predefined sender models or manual configuration allowed
  • Buttons: START/ STOP/ TEST/ AUTO/ MAN/ RESET-OFF/ HELP/ GEN
  • Choice of 5 languages
  • Events, help & alarm text are editable
  • Information on status, alarms and events
  • Events and data recording
  • Automatic call* to a remote PC on specific fault or event
  • More then 125 system parameters in flash memory
  • Help menu for explanation of the remaining operation
  • Weekly Exerciser
  • Modbus protocol available for PLC communication
  • Fast setup on site by the controller keypad or by using an Windows software*
  • Powerful software* available for programming, controlling and monitoring.

OPERATION

List of alarms:
  • Pre-alarm & shutdown on high coolant temperature [analogue]
  • High coolant temperature [digital]
  • individual analogue (4) and digital (1) sender fault
  • Pre-alarm & shutdown on low oil pressure [analogue]
  • Low oil pressure [digital]
  • Pre-alarm & shutdown on low fuel level [analogue]
  • Low fuel level [digital]
  • High, low & very low battery voltage
  • Defective battery charge alternator
  • Speed signal lost (magnetic pickup)
  • Low / high frequency
  • Defective starter
  • Emergency stop
  • Unexpected stop
  • Engine stop failure
  • Low / high generator frequency
  • Low / high generator voltage
  • Asymmetry / short-circuit & generator overload
  • External generator protection tripping
  • Incorrect generator phase sequence
  • Incorrect main phase sequence
  • Incorrect system frequency setting
  • Main / Generator contactor failure
  • System error
  • Maintenance requested
  • Fuel transfer tank empty
  • Fuel transfer tank too full
  • Rent hours exhausted
  • 4 spear faults* Note: * = option
Display – Main screen (like the picture above)
  • Battery voltage (Vdc)
  • CA Current & voltage (3 phases) / frequency / hour meter
  • Fuel level (%) / oil pressure / coolant temperature
  • Maintenance timer (hours)
Display – Other information available
  • Voltage ph. to ph., ph. to neutral for main & generator sides
  • Active, reactive & apparent power / active-reactive energy
  • Power factor for each phase
  • Engine speed (RPM).
  • Total number of starting attempts & percentage of successful starting attempts
  • All parameters & status of the system
  • Event messages & help

RGK50
GENERATING SET CONTROLLER WITH LCD DISPLAY, RS-232, W/O T. SW. CONTROL

Documents English French Spanish
Brochures

p_cg-rgk50_eng
378.11K

p_cg-rgk50_fra
389.30K

Presentations

v_DMG-PD65GB04-10_eng
4.07M

Installation
Manuals
Technicals Informations